Oil Filter – Perkins Engine Model 1104D-E44TAG2, 1104A-44TG2, 1104C-44TAG2, 1104D-44TG1, 1104A-44T
2654407 · Filter / belt
Perkins
List price $82.15
Commercial & Industrial Power Equipment Worldwide
SKU TP-P55-T3-UL
Market compatibility
USA EPA-certified
Tier 3 EPA Certified — Emergency Stationary Applications · Tier 3 – UL Listed
Need help with voltage, frequency or sizing? Talk to a generator specialist or call +1 251-314-4812.
The TP-P55-T3-UL is a 71 kVA / 57 kW standby, 64 kVA / 51 kW prime diesel generator, EPA-certified for the US market.
It uses a Perkins 1104D-44TG1 engine, a Leroy Somer LSA42.3L9 alternator and a Deep Sea DSE 7420 control panel.
It is listed at 60 Hz, 3-phase, with voltages 120/208 and 277/480, in enclosed or open skid configurations.
Global Generator Supply provides Emergency Stationary generators certified to Tier 4i, Tier 3, and Tier 2 ratings, with UL2200, CSA, and other compliance options. Triton can build virtually any generator to spec — gaseous or diesel — and we maintain ready stock of generators built to standard configurations for immediate shipment, along with trailers, transfer switches, and fuel tanks.
Triton EPA Generators are engineered to exacting standards for the US and Canadian markets. We offer options for everything from hurricane zones along the Gulf coast to the harsh climate of the far north. Triton generators are deployed at government facilities, hotels, manufacturing plants, medical facilities, grocery stores, and data centers across North America.
The TP-P55-T3-UL delivers a standby rating of 57 kW / 71 kVA and a prime rating of 51 kW / 64 kVA. The Perkins 1104D-44TG1 is a four-cylinder, turbocharged diesel engine engineered for strong performance and outstanding reliability in both prime and standby power generation applications. Operating at 1800 rpm, it delivers 63 kWm (84 hp), providing an excellent balance of power, fuel efficiency, and long-term durability. At Triton Power, we select engines like the Perkins 1104D-44TG1 because they ensure consistent output, simplified maintenance, and the full support of Perkins’ global parts and service network—making them a trusted solution for demanding environments. The Perkins 1104D-44TG1 pairs with a Leroy Somer alternator, and the Deep Sea DSE 7420 digital control panel makes monitoring and management straightforward. The TP-P55-T3-UL is built to rugged specifications and delivers power exactly where and when you need it.
The TP-P55-T3-UL includes the following standard features:
Triton EPA Generators are compliant for emergency stationary use throughout the United States and Canada. Our generators are engineered to operate in the most challenging environments and can be modified to meet virtually any application. With standalone models ranging from 10 kW to 2,500 kW, paralleled generators up to 20 MW, and the ability to customize a unit to fit any need, your options for durable and reliable power generation are essentially unlimited.
Listed in our industry catalogs: Restaurants & hospitality
Values are shown exactly as published. Anything not listed is marked “Not specified”.
Download full specifications| Triton Model | TP-P55-T3-UL |
|---|---|
| Typical Generator Output | Standby: 71 kVA / 57 kW Prime: 64 kVA / 51 kW |
| Engine Brand | Perkins |
|---|---|
| Engine Model | 1104D-44TG1 |
| Engine Power Output | 65 kWm / 87.15 HP @ 1800 RPM |
| Aspiration | Turbocharged |
| Displacement | 4.41 L |
| Cylinders | 4, in line |
| Speed | 1800 RPM |
| Alternator Brand | Leroy Somer |
|---|---|
| Alternator Model | LSA42.3L9 |
| Insulation Class | H |
| Frequency | 60 Hz |
|---|---|
| Voltages Available | 120/208, 277/480 |
| Control Panel | Deep Sea DSE 7420 |
|---|
| Models Available | Enclosed, Open Skid |
|---|
| Engine Tier Rating | Tier 3 |
|---|---|
| Compliance | UL 2200 Listed, EPA Tier 3, NFPA 110 compatible |
| Dimensions | Not specified |
|---|---|
| Weight | Not specified |
| Configurations | Enclosed, Open Skid |
Dimensions and weight are not published for this model. Ask for the data sheet.
| Emissions | Tier 3 EPA Certified — Emergency Stationary Applications |
|---|---|
| Market | USA EPA-certified |
| UL 2200 | Listed |
Specification sheets, engine and alternator data and brochures for this model, for your engineering and procurement teams.
These parts name this engine model in their own description. Confirm your engine serial number when ordering.
2654407 · Filter / belt
Perkins
List price $82.15
26510342 · Filter / belt
Perkins
List price $106.02
4816636 · Filter / belt
Perkins
List price $87.66
Our engineers match transfer switches, fuel systems and trailers to this generator's rating when you request a quote.
Same market and frequency, nearest in size. Tick up to three to compare with this model.
TP-55-T3
Engine Perkins
TP-P65-T3-UL
Engine Perkins
TP-NG40-S-K-UL
Engine PSI
TP-Y40-T4i-SGUL
Engine Yanmar
| Model | TP-P55-T3-ULThis model | TP-55-T3 | TP-P65-T3-UL | TP-NG40-S-K-UL | TP-Y40-T4i-SGUL |
|---|---|---|---|---|---|
| Standby | 57 kW / 71 kVA | 55 kW / 70 kVA | 65 kW / 81 kVA | 40 kW / 50 kVA | 38 kW / 47 kVA |
| Prime | 51 kW / 64 kVA | 51 kW / 64 kVA | 59 kW / 74 kVA | 34 kW / 44 kVA | 34 kW / 40 kVA |
| Engine | Perkins 1104D-44TG1 | Perkins 1104D-44TG1 | Perkins 1104D-E44TG1 | PSI Engine 4.3L | Yanmar 4TNV98T |
| Alternator | Leroy Somer LSA42.3L9 | Leroy Somer | Leroy Somer LSA44.3S4 | — | Stamford |
| Control panel | Deep Sea DSE 7420 | — | Deep Sea DSE 7420 | — | — |
| Frequency | 60 Hz | 60 Hz | 60 Hz | 60 Hz | 60 Hz |
| Voltages | 120/208, 277/480 | 120/208, 277/480, 120/240 | 120/208, 277/480 | — | 120/208, 277/480, 120/240 |
| Configuration | Enclosed, Open Skid | Enclosed, Open | Enclosed, Open Skid | — | Enclosed, Open |
| Fuel tank | — | — | — | — | — |
| Market | USA EPA-certified | USA EPA-certified | USA EPA-certified | USA EPA-certified | USA EPA-certified |
Tick “Compare” on a model above to add it to this table.
Our team can help configure it for your destination, and quote documentation and shipping on request, or you can use your own forwarder.